XMT-3000 Series Single Input Type Intelligent Temperature Controller

Short Description:

XMT*- 3000 Series digital display temperature control instrumentInstruction ManualXMT*-3000 Series temperature control instrument can replace the traditional pull yards -type or potentiometer type digital display?meter, which uses the touch buttons can freely set, single-row LED display, with a...


Product Detail

Product Tags

XMT*- 3000 Series digital display temperature control instrument

Instruction Manual

XMT*-3000 Series temperature control instrument can replace the traditional pull yards -type or potentiometer type digital display?meter, which uses the touch buttons can freely set, single-row LED display, with a fixed PID control or NO/OFF?return difference control can elect, and return difference?is adjustable, also have sensor error correction function. The instrument have a reliable control performance, cost-effective and wide application and so on.

Ⅰ、Technical Indexs:

1、Input type and measuring range:

?K(0~1300℃) ?E(0~800℃) S(400~1600℃) ?J(0~1000℃)

B(800~1800℃)Pt100(-50.0~200.0℃; -200~600℃) ??Cu50(-50.0~150.0℃)

Note: The instrument input type and measuring range subject to the meter label.

2、Display accuracy:±1%F·S±1B ???Additional cold junction compensation error≤2℃

3、Control mode:ON/OFF?control(return difference?is adjustable)or PID?control

4、Setting range of return difference: 1~20℃,

5、Control proportion band(P):±9℃?or ±0.9℃?when temperature display has decimal point.

6、PID control period:30 seconds

7、Sensor error translation scope amendment:-20~20℃

8、Output mode:Relay contact capacity AC220V/5A;?Drivng solid relay signal:driving electric current ≥ 15mA,voltage ≥ 9V

9、Power:AC85~242V ?50Hz/60Hz ??

Power consumption: less than 3W or other according to customer requirement

10、Work environment:temperature 0~50.0℃, relative humidity ≤ 85%RH, without corrode and strong electric radiation.

Ⅱ、Instrument panel(consult):

11

、Parameter?setting

3.1、Set value?of temperatureUnder the normal?display state, directly press the data increasing key(▲)or data decreasing?key(▼)to display the temperature set value, this time press (▲) or (▼) key to change the temperature set value, long pressing enables the data fast plus or minus. Without any operating conditions, the set value flashes 8 times and returnto normal display status.

3.2、Parameter modificationUnder the normal?display state, at the same time pressing(▲)and(▼)can display the sensor error correction symbol “SC”, in three seconds pressing (▲) or (▼) key will display and can modify the parameter value; if then again pressing(▲)and(▼)can display the control return difference?symbol “HY”,?in three seconds pressing (▲) or (▼) key will display and can modify the parameter value; again press the (▲) and (▼) key to exit and return to the the normal display status.?

When display parameter symbol, in 3 seconds without any operation, the meter will return to the normal display; in the display parameters cases, if the set value flashes 8 times without any operation,the meter also will return to normal display.

3.3、Contro modeDisconnect the meter control selection terminals,the meter is two?place?control; Connect the meter control selection terminals,the meter will automatically switch to PID control.

、Control Output

When the meter is ON/OFF?control:

When the measured temperature value <?(set value-return difference?),the relay total and low pass, total and high cut, while OUT indicator is light, the heater work;

When the measured temperature value >(set value+return difference?),the relay total and low cut, total and high pass, while OUT indicator is out, the heater stop working;

When the meter is PID control:The meter implement control output according to the fixed PID value and control cycle.

、Model Sense

XMT □ - 3 □ □ □ -Suffix

1?????2 ?3 ?4

Blank 1External size and Installation hole(mm):? ?‘Empty’:80×160×80 ?76×152;?????

‘S’:160×80×80 ??152×76;???‘A’:96×96×80 ???92×92;????‘B’:60×120×105 ?56×114;??

‘E’:48×96×80 ??44×92;?????‘F’:96×48×80 ???92×44;????‘D’:72×72×100 ??68×68;?????

?‘G’:48×48×90 ??44×44;‘K’:24×48×90 ???23×45 ?????

Blank 2Control output mode:

‘0’:?two?place?control,relay output;??‘4’:?fixed PID control,relay output;

‘5’:?Drivng solid relay signaloutput;???7’:?Drivng?SCR zero passed?pulse signal output

Blank 3Alarm mode:?‘0’:no alarm; ???‘1’:one upper limit alarm;

Blank 4Input mode:??‘1’:?Thermocouple;??‘2’:?resistance????

Suffix:‘D’:?30A high-power relay output

、Error

When the meter display window display “-HH-” or “-LL-”, indicate that the channel sensor measured value overload or the sensor have been bad, should examine and repair the sensor, if the sensor have no trouble,?please check?that the selected sensor is consistent with the meter input type.

、Wiring diagram (consult)

3

Note:?Our company will continue to improve product technology, design specification. If change, please subject to?the material object, without notice.


  • Previous:
  • Next:

  • Related Products

    成·人免费午夜无码视频在线观看_疼死了大粗了放不进去视频_亚洲欧美色一区二区三区_欧洲少妇性喷潮_18禁无码永久免费无限制网站 <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <蜘蛛词>| <文本链> <文本链> <文本链> <文本链> <文本链> <文本链>